首页 | 本学科首页   官方微博 | 高级检索  
   检索      


The effect of a self-regulating trace heating element on Legionella within a shower
Authors:T Makin  C A Hart
Institution:Department of Medical Microbiology, University of Liverpool, UK.
Abstract:A self-regulating trace heating element was assessed for its ability to maintain a temperature of 50 degrees C in the mixer valve and dead-legs of a shower, and for its effect on legionellas colonizing the shower. The trace heating element maintained a temperature of 50 degrees C +/- 1.5 degrees C in dead-legs when the circulating hot water supply remained above 45 degrees C. Legionellas appeared in a trace heated dead-leg when the temperature of the dead-leg reached 45 degrees C and the hot water supply dropped below this temperature. Legionellas were eradicated or significantly reduced in sections of the shower where a temperature of 50 degrees C was consistently achieved. The mixer valve which was trace heated but not insulated remained colonized with Legionellas. Legionellas were found in shower water throughout the study.